Siemens TCP

The S7 protocol (RFC 1006) enables read and write access to data blocks, flags, inputs, and outputs of Siemens controllers.

Connection Parameters

Hostname Hostname or IP address
Port TCP port (default: 102)
Rack Rack number (usually 0)
Slot Slot within the rack (typically 2 for S7-300 and S7-400)

Configure Symbols

Each symbol to be read or written must be configured. To create a new symbol, click New Row.

Name Enter the name for display in AnyViz
Area Specifies the memory area of the variable, e.g., Input, Output, Flags, or DB (data blocks)
DB When selecting DB, the number of the data block must be specified
Data type Select the appropriate data type
Address Enter the byte address in decimal notation or the bit address

Bit Addressing

Siemens TCP allows reading or writing individual bits. In Siemens notation, the 21st input bit is labeled as [2.4], which means bit 4 of byte 2. Select the data type BIT and enter the address 2.4.

System Requirements

To communicate with a Siemens PLC via the RFC1006 protocol, the following settings must be configured in the TIA Portal.

Allow Full Access in CPU Properties
Allow full access in TIA Portal
Permit access with PUT/GET
Enable PUT/GET communication in TIA Portal
Disable Optimized Block Access
Disable optimized block access in TIA Portal